Systems #9 is approximately 2-3lbs low on charge. System #7 is completely voided on refrigerant, 10lbs of R410 is needed for #7. Recommends ac leak freeze to stop or slow down the leak on both systems to get both systems running for now. Checked pressures and delta T for both kitchen unit and dinning unit (#7 and #9). System #7 has a leaking indoor evaporator coil, and #9 was on hard lock out due to low refrigerant pressures and was starting to freeze up. Tech recommended AC leak freeze on both systems and charging them up to get them back cooling. #7 needs an evaporator coil, pricing to replace it will have to be emailed to lumenant for approval, Colby will be notified of the findings as well. Tech received approval per Jeff cupp for todays repairs. System #7 has been down for months, findings were reported in the past along with other repairs. Office will be notified to re-confirm the findings. Both systems are back cooling.

Jesse J.
Tech preformed CMA INSPECTION on 20 Split Systems and 8 Mini Split Systems. Split System #14 operates in heat mode but faults out with low pressure fault due to failed cooling TXV. Tech has attached estimate to invoice for cost of replacing TXV. Tech will also have office contact with proposal to replace system for comparison. Split System #7 is still down due to previous diagnosis of leaking evaporator coil found in July of 2023. Split System #13 does operate but primary drain pan is broken in several places. System will have to be evacuated and evaporator coil removed to replace drain pan. Proposals for Split Systems #7 and #13 were sent in August of 2023. All other systems are operating at this time but require minor repairs. Tech has created estimates for minor repairs needed and attached them to invoice. Tech found from previous CMA visit in July of 2023 that all auxiliary drain pans did not have drain lines. Tech recommends adding drain lines to auxiliary pans and connecting them