Trenton NC Heating Air & Conditioning Services
Jackson and Sons has been serving the heating and air conditioning needs of Trenton, NC residents and businesses since 1974.
Our reviews below from your neighbors in Trenton, NC tell the story of our quality, dedication and commitment to customer service.
Local Reviews
for Trenton, NC
Customers say: The recent reviews exhibit a positive overall sentiment, with a slight inclination towards the positive. The reviewers express satisfaction with the services provided, highlighting the helpfulness, expertise, and professionalism of the technicians. They mention the timeliness, efficiency, and quality of the work done. Additionally, the reviewers appreciate the courteous and respectful behavior of the technicians, as well as their willingness to answer questions and provide detailed explanations. The positive reviews also mention the positive experiences with the company's customer service, including the ease of scheduling appointments, the clarity of the pricing, and the overall positive impression left by the technicians. However, it's worth noting that the negative reviews are fewer in number and do not contain any significant negative sentiment. Overall, the reviews suggest that customers have had positive experiences with Jackson and Sons and would recommend their services to others.
Our Reviews by City
Friendly and Professional!
Sabrina - Trenton, NC 28585
Kyle did a great job! Very professional!
Excellent, very professional and knowledgeable
MISTY - Trenton, NC 28585
I love Jackson & Son”s. They have been nothing but a blessing to me and my kids. Everyone is so nice and professional. They have truly been great to me. I wish each and every employee nothing but the best. They have improved my quality of life and I’m thankful.
Excellent
MISTY - Trenton, NC 28585
He was prompt. Listened to my issues and he was so professional that he knew how to solve the problem. His knowledge and experience truly showed. Great guy. Great company #1
Excellent
MISTY - Trenton, NC 28585
He was prompt and on time. Very professional and courteous. Very helpful and friendly.
Great service!
Sabrina - Trenton, NC 28585
Kenny was polite and professional.
Randy is top notch
Curtis Media - Trenton, NC 28585
Love working with Randy. He’s knowledgeable, quick, and really easy to talk to
Great Service; Very Positive Attitude
WRNS-FM - Trenton, NC
Matt was thorough; explained the repair and was very professional.
Great Service
Al - Trenton, NC 28585

David S.
—Performed a CMA Full Service on 1 Wall Mount and 1 Split AC System. —Wall Mount AC - Marvair: Blower motor bearing has a loud noise. Motor may be due for failure. Video on related form under “Blower Section”. Office should provide estimate for motor replacement upon request. —Both systems operating at this time.

Ricardo T.
Tech washed and serviced unit and found no challenges at this time. Customer renewed PSA 1 system.

Alex R.
Replaced 8 angle stops in the house to pex style.

Noah C.
Tech drained water from bathroom branch line and sealed. Vent now has airflow and no more water sounds. Recommended investing in maintenance agreement.

Alex R.
Went under house and cleared grease from the main kitchen line from a clean out.

Joseph C.
Tech returned and repaired collapsed ducts.

Joseph C.
Tech arrived and found no airflow coming from vents on back side of house, tech found major water leak in crawl space caused supply line to collapse and fill with water. Water leak will need to be addressed first husband is a plumber so he is going take car of it. Tech left quote for duct repair 4feet of 12in flex and fix three way splice.

Kyle W.
Installed PlasmaPure whole house air purifier.

Kyle W.
Performed ESA on (1) Bryant Split Heat Pump System. Re-taped loose insulation from air handler panel. Left extra filters with Mr. Strickland. Built estimate for PlasmaPure air purifier due to small amount of mildew substance within in air handler before cleaning. System is operating and draining properly.

Percy M.
PERFORMED CMA FULL SERVICE ON 3 SPLIT SYSTEMS. SPLIT SYSTEM #1 FAN CAPACITOR RATED FOR 5mf TESTED WEAK AT 3.82mf. CAPACITOR DUE FOR FAILURE, RECOMMEND REPLACEMENT OF CAPACITOR. THERE IS AN ESTIMATE PROVIDED FOR REPLACEMENT OF CAPACITOR FOR SPLIT SYSTEM #1. ALL SYSTEMS ARE PERFORMING PROPERLY AND COOLING PROPERLY AT THIS TIME. CLEANED SYSTEMS CONDENSER AND EVAPORATOR COILS, ALSO COMPLETED FILTER CHANGE AND FLUSHED ALL DRAIN LINES. THERE ARE PICTURES AND A PERFORMANCE REPORT ATTACHED TO THIS INVOICE.

Caleb S.
Emailed proposal. Customer has other quotes scheduled and will call back once they make a decision.

Joseph C.
Tech arrived and found system and thermostat operating properly, tech pulled t stat off wall and found lots of moisture in thermostat. Tech found hot humid air coming in from hole behind t stat, tech sealed with foam insulation and sealant. No further challenges at this time

Derek J.
Upon arrival tech sealed hood from where underpinning was installed. Tech also replaced FP5000 with new VP8000 and wired for second stage. System is back operational at this time.

Spencer C.
Tech found system operating properly but customer stated thermostat just came back on and was showing an error before. Based on previous techs notes, tech suspects thermostat issue. Tech also found bugs in thermostat. Tech replaced thermostat and verified system is operating properly. Contactor warranty.

Joseph C.
Tech found system cooling properly upon arrival, tech noticed high humidity and found the fan was in the on position tech put back to auto system dropped 2 degrees while tech was on site. Customer explained issues with thermostat and it sounds like it had a t stat sensor error.

Kyle W.
SYSTEM SET ON 60 UPON ARRIVAL. FOUND COMPRESSOR DRAWING PEAK OF AMP DRAW RATING, AND SYSTEM RUNNING HIGH HEAD PRESSURE DUE TO EXTREMELY CLOGGED CONDENSER COILS. FILTER COMPLETELY CLOGGED AS WELL. INVESTED IN PSA (1) SYSTEM. PERFORMED 1ST VISIT PER OFFICE. AMP DRAWS/PRESSURE BACK TO SPECS. SYSTEM IS 22 YEARS OLD AND MAJORITY OF CRAWLSPACE INSULATION HAS FALLEN, EXPOSING METAL DUCTS. CANNOT GUARANTEE SYSTEM PERFORMANCE ESPECIALLY ON HOT DAYS. SET TO 69 PER REQUEST.

David S.
-Performed CMA Inspection on 1 Trane Split AC System and 1 Marvair wall Mount AC System. -Found no challenges with systems. Operating correctly at this time. Filter count/size should be updated per equipment list.
Sherrill Wayne T.
4 TON GOODMAN SPLIT SYTEM HEAT PUMP

Kenny C.
Performed ESA, no issues at todays visit. Landscaping around system is in very poor condition. Poison ivy was located all around unit. Could not access certain parts of the system due to shrubs and poison ivy. Tech serviced unit the best as possible. Renewal to be billed out.

Matthew L.
Tech found split system condenser not running due to a failed 35/5uf dual run capacitor. Customer approved housecall and capacitor. Renewed agreement on 2 system MSA. Put card on file. Next visit in 6 months. System is back cooling. Put warranty label on capacitor.

Kyle W.
FOUND EVAPORATOR COIL DRIPPING INTO RETURN PLENUM DUE TO LOW R22 CHARGE/HEAVY CORROSION. SYSTEM IS 35 YEARS OLD EVAPORATOR COIL IS UNAVAILABLE FOR REPLACEMENT. HANDED OVER TO FIELD SUPERVISOR. UNABLE TO CONTACT TIM. MANAGEMENT REFERRED MRS. PRESLEY, WHO PAID FOR TODAYS VISIT VIA PHONE. PRESLEY- (704)-986-7242 CALL WITH PROPOSAL.

Kyle W.
22 YEAR OLD R22 SYSTEM. FOUND OUTDOOR FAN MOTOR BEARINGS FAILING CAUSING HIGH AMP DRAW. DUAL RUN CAPACITOR WEAK. BLOWER CAPACITOR LEAKING OIL. COMPRESSOR WINDINGS IN CAUTION RANGE/OVER AMPING. EVAPORATOR COILS HEAVILY RUSTED. HANDED OVER TO FIELD SUPERVISOR.

Kyle W.
RECOVERED REMAINING REFRIGERANT, REPAIRED LEAK AT DISCHARGE LINE, AND REPLACED FILTER DRIER. PASSED BOTH PRESSURE/VACUUM TESTS. ADDED FACTORY CHARGE OF 12LBS R410A. CYCLED IN HEATING/COOLING. PRESSURES WELL WITHIN SPECS. NO LEAK PRESENT AT TXV LINE. MOVED LINE AWAY FROM DISCHARGE TO PREVENT FURTHER RUBBING AND TAPED. WARRANTY.

Kyle W.
FOUND SYSTEM ALMOST VOID OF REFRIGERANT UPON ARRIVAL. LOCATED OBVIOUS LEAK WHERE INDOOR TXV DISTRIBUTOR LINE ENTERS SUCTION LINE DUE TO VIBRATION RUBBING THROUGH. NEED TO ORDER AND REPLACE INDOOR TXV ASSEMBLY. CHARGED SYSTEM WITH 11LBS OF R410A FOR TIME BEING PER OFFICE. SYSTEM COOLING/HEATING AT THIS TIME. INVESTED IN ESA (1) SYSTEM.

Matt C.
Tech washed and seen unit Customer will call in and renew